Joint Policy-Elevators

MEMORANDUM
DATE: January 4, 1999
TO: Building Officials Fire Departments Elevator Contractors Designers Sprinkler Contractors
FROM: Thomas R. Joachim
State Building Codes & Standards Division
Thomas R. Brace
State Fire Marshal Division
SUBJECT: FIRE PROTECTlON - ALL ELEVATOR SYSTEMS

It is the cooperative intent of the State Building Codes & Standards Division and the State Fire Marshal Division to provide uniformity in design, installation and injection of elevator and automatic fire protection systems in the State of Minnesota.
TRACTION (CABLE) TYPE ELEVATORS - FIRE SPRINKLERS ARE NOT REQUIRED IF THE FOLLOWING CONDITIONS ARE MET:

Automatic fire sprinkler protection is not required at the top of the shaft if the shaft is of noncombustible construction. See MSBC 1305.0704 subp.6/MUFC Sec. 1003.4.

Automatic fire sprinkler protection is not required at the bottom of the shaft if the shaft is of noncombustible construction and does not contain combustible hydraulic fluid. See MSBC 1305.0704 subp.I/NFPA-13-1996,4-13.5.1, exception.

Automatic fire sprinkler protection is not required in the machine rooms of traction type elevators when the rooms are located on the top of the elevator shaft and are separated from other areas of the building, other than the shaft, by not less than one hour fire-resistive occupancy separation. See MSBC 1305.0704 subp.6@C Sec. 1003.4.

HYDRAULIC TYPE ELEVATORS - AUTOMATIC FIRE SPRINKLER PROTECTION REQUIREMENTS:

Automatic fire sprinkler protection is required at the bottom of the shaft. The sidewall sprinkler head shall be positioned not more than 2 ft. above the floor of the pit. See MSBC 1305.0704 subp.I/NFPA-13-1996,4-13.5.1.

Automatic fire sprinkler protection is required in elevator equipment rooms. The ASME Al 7.1 code requires the disconnection of power (shunt trip breakers) to the elevator prior to the application of water in elevator machine rooms or hoistways.

This disconnection is normally accomplished by a heat detector (located adjacent to the sprinkler head) with sufficient sensitivity to operate the shunt trip breakers prior to the activation of the sprinklers. See NFPA-72-1993, sec. 3-8.16.

The new elevator code, expected to be adopted in early 1999, contains an exception: If sprinklers are added in an existing elevator machine room or hoistway, automatic disconnect of the main power supply is not required if the existing elevator is hydraulic, installed prior to the adoption of ASME A17.1-1996, and equipped with Phase I and Phase Il firefighter's service in compliance with Rules 211.3 through 211.9.
(This exception will not apply when the elevator itself is being altered.)

Water flow control valves and/or tamper switches are currently required on pipe feeding sprinkler heads located in the elevator shaft or equipment room.

(Note: The new ASME Al 7.1-1996 edition will delete this requirement. This code is expected to be adopted in early 1999.)

Automatic fire sprinkler protection is not required at the top of the shaft if it is of noncombustible construction. Elevator car enclosure materials shall meet the requirements of ASME A17.1, Safety Code for Elevators and Escalators. See MSBC 1305.0704 subp.6/MUFC Sec. 1003.4 and NFPA- 13-1996, 4-13.5.3, exception.

TRACTION AND HYDRAULIC TYPE ELEVATORS:

The only sprinkler piping that shall be allowed in the equipment room or in the pit is the actual line piping feeding the sprinkler head(s). No crossmain, bulk runs or risers shall be routed through these area.

Should you have any questions or need further information, please feel free to contact David Stegura at 651.215.0514 or Elroy Berdahl at 651.297.7081.
Sincerely,
Thomas R. Joachim
State Building Official
Thomas R. Brace
State Fire Marshal

Send mail to: with questions or comments about this web site. © Copyright 2008
Powered By